How the wire size is chosen
The calculator checks two things and recommends the larger of the two sizes:
- Voltage drop. It works out the most resistance the wire may have, then picks the first size in NEC Chapter 9, Table 8 (75 °C, stranded) that is at or below it.
- Ampacity. It picks the first size whose NEC Table 310.16 ampacity covers the current (125% of it for a continuous load), and that also respects the small-wire breaker limits in NEC 240.4(D). It uses the column you pick: 60 °C by default, or 75 °C if the breaker and equipment terminals are marked for 75 °C.
60 °C or 75 °C?
NEC 110.14(C)(1)(a) says that circuits rated 100 A or less, and wire from 14 to 1 AWG, must use the 60 °C ampacity unless the terminals are listed and marked for 75 °C. NM cable (Romex) is limited to 60 °C ampacity by NEC 334.80 in any case. Many breakers and panels are marked 60/75 °C, so check the label. Above 100 A, 110.14(C)(1)(b) allows the 75 °C column, and the calculator switches to it.
The choice can change the answer. A 40 A continuous load needs 40 × 1.25 = 50 A of ampacity. In the 60 °C column, 8 AWG copper is only 40 A, so you need 6 AWG copper (55 A). In the 75 °C column, 8 AWG copper (50 A) is enough.
(use 1.732 instead of 2 for three-phase)
Worked example
A 20 A, 120 V load is 100 ft away and you want no more than 3% drop. 3% of 120 V is 3.6 V. Max resistance = 3.6 × 1,000 ÷ (2 × 100 × 20) = 0.9 Ω per 1,000 ft. 10 AWG copper is 1.24 Ω (a 4.96 V drop, 4.13%), which is too high. 8 AWG copper is 0.778 Ω: 2 × 100 × 20 × 0.778 ÷ 1,000 = 3.11 V, or 2.59%. Its 60 °C ampacity is 40 A, well over 20 A, so the answer is 8 AWG copper.
Wire table used
| Size | Copper (Ω per 1,000 ft) | Aluminum (Ω per 1,000 ft) | Copper 60 °C | Copper 75 °C | Aluminum 60 °C | Aluminum 75 °C |
|---|---|---|---|---|---|---|
| 14 AWG | 3.14 | 5.17 | 15 A | 20 A | not listed | not listed |
| 12 AWG | 1.98 | 3.25 | 20 A | 25 A | 15 A | 20 A |
| 10 AWG | 1.24 | 2.04 | 30 A | 35 A | 25 A | 30 A |
| 8 AWG | 0.778 | 1.28 | 40 A | 50 A | 35 A | 40 A |
| 6 AWG | 0.491 | 0.808 | 55 A | 65 A | 40 A | 50 A |
| 4 AWG | 0.308 | 0.508 | 70 A | 85 A | 55 A | 65 A |
| 3 AWG | 0.245 | 0.403 | 85 A | 100 A | 65 A | 75 A |
| 2 AWG | 0.194 | 0.319 | 95 A | 115 A | 75 A | 90 A |
| 1 AWG | 0.154 | 0.253 | 110 A | 130 A | 85 A | 100 A |
| 1/0 AWG | 0.122 | 0.201 | — | 150 A | — | 120 A |
| 2/0 AWG | 0.0967 | 0.159 | — | 175 A | — | 135 A |
| 3/0 AWG | 0.0766 | 0.126 | — | 200 A | — | 155 A |
| 4/0 AWG | 0.0608 | 0.1 | — | 230 A | — | 180 A |
| 250 kcmil | 0.0515 | 0.0847 | — | 255 A | — | 205 A |
| 300 kcmil | 0.0429 | 0.0707 | — | 285 A | — | 230 A |
| 350 kcmil | 0.0367 | 0.0605 | — | 310 A | — | 250 A |
| 400 kcmil | 0.0321 | 0.0529 | — | 335 A | — | 270 A |
| 500 kcmil | 0.0258 | 0.0424 | — | 380 A | — | 310 A |
| 600 kcmil | 0.0214 | 0.0353 | — | 420 A | — | 340 A |
| 700 kcmil | 0.0184 | 0.0303 | — | 460 A | — | 375 A |
| 750 kcmil | 0.0171 | 0.0282 | — | 475 A | — | 385 A |
| 1000 kcmil | 0.0129 | 0.0212 | — | 545 A | — | 445 A |
The 60 °C column is shown only to 1 AWG: larger wire serves circuits over 100 A, where the 75 °C column applies. Small conductors are limited by NEC 240.4(D) regardless of the table: 14 AWG copper to a 15 A breaker, 12 AWG copper to 20 A, 10 AWG copper to 30 A, 12 AWG aluminum to 15 A and 10 AWG aluminum to 25 A. The calculator applies these limits.
What this doesn't cover
This is an estimate, not a substitute for the electrical code or an electrician. Real wire sizing also depends on:
- the actual temperature rating of the terminals, which you set above (if you aren't sure, leave it at 60 °C);
- corrections for hot locations and for more than three current-carrying wires in a conduit or cable (NEC 310.15);
- other wiring-method limits, such as for UF cable or wire in a hot attic;
- rules for specific equipment, such as motors, air conditioners, EV chargers and services, which have their own sizing articles.
Check your local code and the equipment's instructions, and have a licensed electrician design and inspect the circuit.
Sources
- Michigan State University, Electrical Tech Note 212: resistance of stranded wire at 75 °C (from NEC Table 8)
- IAEI Magazine: Voltage drop calculations (formulas and NEC informational notes)
- Cerrowire: Ampacity charts (NEC Table 310.16)
- NFPA 70, National Electrical Code
- Omni Cable: NEC ampacity data, Table 310.15(B)(16) with 60 °C, 75 °C and 90 °C columns for copper and aluminum