Wire size calculator

Enter the load, distance and voltage to get the smallest wire that keeps the voltage drop under your target and can carry the current.

Private: calculated on your device. Nothing you type is sent anywhere.

Next: Want to check a wire you already have? Use the voltage drop calculator. Not sure of the current? Total it in the electrical load calculator.

How the wire size is chosen

The calculator checks two things and recommends the larger of the two sizes:

  1. Voltage drop. It works out the most resistance the wire may have, then picks the first size in NEC Chapter 9, Table 8 (75 °C, stranded) that is at or below it.
  2. Ampacity. It picks the first size whose NEC Table 310.16 ampacity covers the current (125% of it for a continuous load), and that also respects the small-wire breaker limits in NEC 240.4(D). It uses the column you pick: 60 °C by default, or 75 °C if the breaker and equipment terminals are marked for 75 °C.

60 °C or 75 °C?

NEC 110.14(C)(1)(a) says that circuits rated 100 A or less, and wire from 14 to 1 AWG, must use the 60 °C ampacity unless the terminals are listed and marked for 75 °C. NM cable (Romex) is limited to 60 °C ampacity by NEC 334.80 in any case. Many breakers and panels are marked 60/75 °C, so check the label. Above 100 A, 110.14(C)(1)(b) allows the 75 °C column, and the calculator switches to it.

The choice can change the answer. A 40 A continuous load needs 40 × 1.25 = 50 A of ampacity. In the 60 °C column, 8 AWG copper is only 40 A, so you need 6 AWG copper (55 A). In the 75 °C column, 8 AWG copper (50 A) is enough.

Max resistance (Ω per 1,000 ft) = target % ÷ 100 × volts × 1,000 ÷ (2 × length × amps)
(use 1.732 instead of 2 for three-phase)

Worked example

A 20 A, 120 V load is 100 ft away and you want no more than 3% drop. 3% of 120 V is 3.6 V. Max resistance = 3.6 × 1,000 ÷ (2 × 100 × 20) = 0.9 Ω per 1,000 ft. 10 AWG copper is 1.24 Ω (a 4.96 V drop, 4.13%), which is too high. 8 AWG copper is 0.778 Ω: 2 × 100 × 20 × 0.778 ÷ 1,000 = 3.11 V, or 2.59%. Its 60 °C ampacity is 40 A, well over 20 A, so the answer is 8 AWG copper.

Wire table used

SizeCopper (Ω per 1,000 ft)Aluminum (Ω per 1,000 ft)Copper 60 °CCopper 75 °CAluminum 60 °CAluminum 75 °C
14 AWG3.145.1715 A20 Anot listednot listed
12 AWG1.983.2520 A25 A15 A20 A
10 AWG1.242.0430 A35 A25 A30 A
8 AWG0.7781.2840 A50 A35 A40 A
6 AWG0.4910.80855 A65 A40 A50 A
4 AWG0.3080.50870 A85 A55 A65 A
3 AWG0.2450.40385 A100 A65 A75 A
2 AWG0.1940.31995 A115 A75 A90 A
1 AWG0.1540.253110 A130 A85 A100 A
1/0 AWG0.1220.201—150 A—120 A
2/0 AWG0.09670.159—175 A—135 A
3/0 AWG0.07660.126—200 A—155 A
4/0 AWG0.06080.1—230 A—180 A
250 kcmil0.05150.0847—255 A—205 A
300 kcmil0.04290.0707—285 A—230 A
350 kcmil0.03670.0605—310 A—250 A
400 kcmil0.03210.0529—335 A—270 A
500 kcmil0.02580.0424—380 A—310 A
600 kcmil0.02140.0353—420 A—340 A
700 kcmil0.01840.0303—460 A—375 A
750 kcmil0.01710.0282—475 A—385 A
1000 kcmil0.01290.0212—545 A—445 A

The 60 °C column is shown only to 1 AWG: larger wire serves circuits over 100 A, where the 75 °C column applies. Small conductors are limited by NEC 240.4(D) regardless of the table: 14 AWG copper to a 15 A breaker, 12 AWG copper to 20 A, 10 AWG copper to 30 A, 12 AWG aluminum to 15 A and 10 AWG aluminum to 25 A. The calculator applies these limits.

What this doesn't cover

This is an estimate, not a substitute for the electrical code or an electrician. Real wire sizing also depends on:

  • the actual temperature rating of the terminals, which you set above (if you aren't sure, leave it at 60 °C);
  • corrections for hot locations and for more than three current-carrying wires in a conduit or cable (NEC 310.15);
  • other wiring-method limits, such as for UF cable or wire in a hot attic;
  • rules for specific equipment, such as motors, air conditioners, EV chargers and services, which have their own sizing articles.

Check your local code and the equipment's instructions, and have a licensed electrician design and inspect the circuit.

Sources

How we checked this

Before every update, this calculator is run in a real browser with these known answers, and it must match all of them:

  • 20 A at 120 V, 100 ft, copper, 3%: 10 AWG drops 4.96 V (4.13%), so 8 AWG ✓
  • 15 A at 120 V, 50 ft, copper, 3%: 12 AWG (1.98 Ω/kft ≤ 2.4 allowed) ✓
  • 40 A at 240 V, 150 ft, aluminum, 3%: 4 AWG aluminum ✓
  • Edge: 100 A over 10 ft with 75 °C terminals is set by ampacity, not drop: 3 AWG copper (100 A at 75 °C) ✓
  • Same 100 A at the default 60 °C rating: 3 AWG is only 85 A, so 1 AWG copper (110 A) ✓
  • 40 A continuous needs 50 A: at 60 °C 8 AWG is 40 A, so 6 AWG copper (55 A) ✓
  • Same 40 A continuous with 75 °C terminals: 8 AWG copper (50 A) ✓
  • Aluminum at 60 °C: 30 A over 10 ft needs 35 A, so 8 AWG aluminum ✓
  • Edge: a 0% target is refused ✓

Last checked October 26, 2026. Spotted something wrong? The math is done in your browser with the formula shown on this page, so you can check any result by hand.

Add this calculator to your website (free)

Paste this code into any web page. The calculator works on your page, resizes itself, has no ads and no tracking cookies, and nothing your visitors type is sent anywhere. More about embedding.

Questions people ask

What size wire for 20 amps at 100 feet?

At 120 V with a 3% voltage drop target, 8 AWG copper (2.59% drop). 12 AWG is enough for the ampacity, but over 100 ft it would drop 6.6% at 20 A. At 240 V, 10 AWG copper keeps the drop to 2.07%.

What size wire for a 30 amp circuit?

10 AWG copper is the usual minimum for 30 A (NEC 240.4(D)). Long runs may need 8 AWG or larger to keep the voltage drop under 3%.

What size wire for 100 amps?

With 75 °C terminals, 3 AWG copper (100 A) or 1 AWG aluminum (100 A) from Table 310.16. If the terminals are only rated 60 °C, it takes 1 AWG copper (110 A). A long feeder may need a larger size for voltage drop, and dwelling services have their own rules (NEC 310.12).

Is 3% voltage drop required?

No. It comes from informational notes in NEC 210.19(A) and 215.2(A), which are recommendations. It's a widely used design target because larger drops waste energy and can make motors and lights work poorly.

Can I use aluminum wire?

For feeders and large circuits, yes, if the terminals are rated for it (marked AL/CU). It needs to be about two sizes larger than copper for the same current.