Electrical load calculator

List the appliances on a circuit to see the total watts, the amps at 120 V and 240 V, and the smallest standard breaker that covers the load.

Enter each appliance's watts from its nameplate, or pick a typical one.

Private: calculated on your device. Nothing you type is sent anywhere.

Next: Long run to the load? Check the voltage drop and the wire size. Want the running cost? Use the electricity cost calculator.

How the load is worked out

Watts are volts times amps, so dividing the total watts by the voltage gives the current. Then the breaker has to cover the load with room to spare for anything that runs for a long time.

Total watts = Σ (watts × how many)
Amps = total watts ÷ volts
Breaker must be at least: non-continuous amps + 125% × continuous amps

A continuous load is one expected to run at its maximum for 3 hours or more, like a space heater, a water heater or an EV charger. NEC 210.20(A) says the breaker's rating can't be less than the non-continuous load plus 125% of the continuous load. That's the same as saying a continuous load should use no more than 80% of a standard breaker, which is where the "80% rule" comes from (1 ÷ 1.25 = 0.8).

Worked example

A microwave (1,100 W) and a coffee maker (1,000 W) on one kitchen circuit: 2,100 W ÷ 120 V = 17.5 A. Neither runs for 3 hours, so a 20 A circuit covers it. A 1,500 W space heater left on all evening is continuous: 1,500 ÷ 120 = 12.5 A, × 1.25 = 15.6 A, so it needs a 20 A breaker even though 12.5 A is less than 15. On 240 V, 2,100 W draws only 8.75 A.

Add a 1,500 W space heater to the 1,100 W microwave instead: 2,600 W ÷ 120 V = 21.7 A. That's more than 20 A, the largest general-purpose 120 V circuit, so the answer is to put them on separate circuits.

Clothes dryers and electric water heaters are 240 V appliances. When you pick one of those, the calculator gives only the 240 V answer. A 4,500 W water heater draws 4,500 ÷ 240 = 18.75 A. NEC 422.13 treats a storage water heater as a continuous load, so 18.75 × 1.25 = 23.4 A, which rounds up to a 25 A breaker on its own circuit (30 A is also common).

Standard breaker sizes

A circuit that serves more than one load must be rated 15, 20, 30, 40 or 50 A (NEC 210.3), so with two or more loads the calculator rounds up only to those. A circuit for one load can use any standard rating in NEC 240.6(A): 15, 20, 25, 30, 35, 40, 45, 50, 60, 70, 80, 90, 100, 110, 125, 150, 175, 200 A and up. At 120 V, general-purpose circuits are 15 or 20 A, so anything over 20 A at 120 V needs to be split up or moved to 240 V.

Limitations

  • Nameplate watts are a maximum. Many appliances, like refrigerators, cycle on and off and draw less on average, but the circuit still has to handle the peak.
  • Motors start hard. Compressors and pumps draw several times their running current for a moment, and have their own sizing rules (NEC Article 430 and 440).
  • The wire must match the breaker. A 15 A breaker needs at least 14 AWG copper, 20 A needs 12 AWG, and 25 or 30 A needs 10 AWG. Long runs may need larger wire; see the wire size calculator.
  • Not a whole-house load calculation. Sizing a service or panel uses the NEC Article 220 method, with demand factors.

An estimate for planning, not a substitute for the electrical code or a licensed electrician.

Sources

How we checked this

Before every update, this calculator is run in a real browser with these known answers, and it must match all of them:

  • Microwave 1,100 W + coffee maker 1,000 W = 2,100 W: 17.5 A at 120 V ✓
  • Same 2,100 W at 240 V: 8.75 A ✓
  • 1,500 W heater run continuously: 12.5 A × 125% = 15.63 A, so a 20 A breaker at 120 V ✓
  • Space heater 1,500 W + microwave 1,100 W = 2,600 W, 21.7 A at 120 V: too much for one circuit ✓
  • Two 2,700 W loads at 240 V: 22.5 A; NEC 210.3 allows only 15/20/30/40/50 A with more than one load, so 30 A (not 25 A) ✓
  • One 5,400 W load at 240 V: 22.5 A, an individual circuit, so a 25 A breaker ✓
  • Clothes dryer preset is a 240 V appliance: no 120 V breaker is suggested ✓
  • Water heater preset, 4,500 W, continuous by NEC 422.13: 18.75 A × 1.25 = 23.44 A, so 25 A at 240 V ✓
  • Edge: no wattage entered asks for one ✓

Last checked October 26, 2026. Spotted something wrong? The math is done in your browser with the formula shown on this page, so you can check any result by hand.

Add this calculator to your website (free)

Paste this code into any web page. The calculator works on your page, resizes itself, has no ads and no tracking cookies, and nothing your visitors type is sent anywhere. More about embedding.

Questions people ask

How many watts can a 20 amp circuit handle?

At 120 V, 20 × 120 = 2,400 W for loads that don't run continuously. For continuous loads, the 80% rule limits it to 16 A, or 1,920 W.

How many watts can a 15 amp circuit handle?

1,800 W at 120 V, or 1,440 W for continuous loads (80% of 15 A is 12 A).

How do I convert watts to amps?

Divide watts by volts. 1,500 W ÷ 120 V = 12.5 A; at 240 V it's 6.25 A.

What is the 80% rule for breakers?

A standard breaker should carry no more than 80% of its rating for a load that runs 3 hours or more. It's the same requirement as NEC 210.20(A)'s 125% sizing, written the other way round.

Can I run a space heater and a microwave on the same circuit?

Not on one circuit. 1,500 W + 1,100 W = 2,600 W, or 21.7 A at 120 V. That's more than a 20 A circuit, the largest general-purpose 120 V circuit, so it's too much: put them on separate circuits.