How voltage drop is calculated
Every wire has a little resistance, so some voltage is used up pushing current along it. The longer and thinner the wire, and the more current it carries, the bigger the drop. Current flows out and back, so a single-phase circuit counts the length twice. A balanced three-phase circuit uses √3 (1.732) instead of 2.
Three-phase: VD = 1.732 × L × I × R ÷ 1,000
Percent drop = VD ÷ supply voltage × 100
L is the one-way length in feet, I is the current in amps, and R is the wire's resistance in ohms per 1,000 feet. This calculator uses the DC resistance of stranded, uncoated copper and stranded aluminum at 75 °C from NEC Chapter 9, Table 8. That is the same basis as the K factors 12.9 (copper) and 21.2 (aluminum) used in the circular-mil formula.
Worked example
A 120 V, 16 A load sits 100 ft from the panel on 12 AWG copper (1.98 Ω per 1,000 ft). VD = 2 × 100 × 16 × 1.98 ÷ 1,000 = 6.34 V. As a percent: 6.336 ÷ 120 × 100 = 5.28%, so the load sees about 113.7 V. Moving up to 10 AWG (1.24 Ω) gives 2 × 100 × 16 × 1.24 ÷ 1,000 = 3.97 V, or 3.31%.
The 3% and 5% guidelines
Informational notes in the NEC (in 210.19(A) for branch circuits and 215.2(A) for feeders) suggest sizing wire so the drop is no more than 3% on a branch circuit or feeder, and no more than 5% in total from the service to the farthest outlet, for "reasonable efficiency of operation." These notes are advice, not enforceable rules, but most designers follow them. Some equipment, such as fire pumps and sensitive electronics, has its own stricter limits.
Resistance and ampacity used
| Size | Copper (Ω per 1,000 ft) | Aluminum (Ω per 1,000 ft) | Ampacity, copper 75 °C | Ampacity, aluminum 75 °C |
|---|---|---|---|---|
| 14 AWG | 3.14 | 5.17 | 20 A | not listed |
| 12 AWG | 1.98 | 3.25 | 25 A | 20 A |
| 10 AWG | 1.24 | 2.04 | 35 A | 30 A |
| 8 AWG | 0.778 | 1.28 | 50 A | 40 A |
| 6 AWG | 0.491 | 0.808 | 65 A | 50 A |
| 4 AWG | 0.308 | 0.508 | 85 A | 65 A |
| 3 AWG | 0.245 | 0.403 | 100 A | 75 A |
| 2 AWG | 0.194 | 0.319 | 115 A | 90 A |
| 1 AWG | 0.154 | 0.253 | 130 A | 100 A |
| 1/0 AWG | 0.122 | 0.201 | 150 A | 120 A |
| 2/0 AWG | 0.0967 | 0.159 | 175 A | 135 A |
| 3/0 AWG | 0.0766 | 0.126 | 200 A | 155 A |
| 4/0 AWG | 0.0608 | 0.1 | 230 A | 180 A |
| 250 kcmil | 0.0515 | 0.0847 | 255 A | 205 A |
| 300 kcmil | 0.0429 | 0.0707 | 285 A | 230 A |
| 350 kcmil | 0.0367 | 0.0605 | 310 A | 250 A |
| 400 kcmil | 0.0321 | 0.0529 | 335 A | 270 A |
| 500 kcmil | 0.0258 | 0.0424 | 380 A | 310 A |
| 600 kcmil | 0.0214 | 0.0353 | 420 A | 340 A |
| 700 kcmil | 0.0184 | 0.0303 | 460 A | 375 A |
| 750 kcmil | 0.0171 | 0.0282 | 475 A | 385 A |
| 1000 kcmil | 0.0129 | 0.0212 | 545 A | 445 A |
Resistance: NEC Chapter 9, Table 8, DC resistance at 75 °C for stranded conductors (solid 14–8 AWG wire is a little lower, so the drop shown is slightly conservative for solid NM cable). Ampacity: NEC Table 310.16, 75 °C column, for not more than three current-carrying conductors at 30 °C ambient. Small wire also has breaker limits under NEC 240.4(D): 15 A for 14 AWG copper, 20 A for 12 AWG copper, 30 A for 10 AWG copper, 15 A for 12 AWG aluminum and 25 A for 10 AWG aluminum.
Getting a realistic number
- Measure the real route. Wire goes up walls and around corners, so it's usually longer than a straight line.
- Use the actual load, not the breaker size, unless you're designing for the worst case.
- AC effects are ignored. For large conductors in steel conduit, reactance adds to the drop; NEC Chapter 9, Table 9 gives AC values. For small branch-circuit wire the difference is usually small.
- Hot wire has more resistance. Table 8 values are for 75 °C. A lightly loaded wire runs cooler, so its real drop is a bit less.
This is an estimate to help plan. Local codes and the equipment maker's instructions come first, and a licensed electrician should design and inspect any real installation.