How generator size is worked out
Generators have two ratings: running (rated) watts they can supply continuously, and starting (surge) watts they can supply for a few seconds. Motors in refrigerators, pumps and air conditioners need several times their running watts to start.
Starting watts needed = sum of running watts + the biggest extra start-up surge (starting − running) of any one item
Recommended rating = each figure × (1 + margin)
This follows Cummins' method: add all the running watts, then take the starting watts of the largest motor plus the running watts of everything else. You don't add every starting figure, because motors rarely start at the same moment.
Worked example
Cummins' RV example: an air conditioner (1,800 W running, 2,800 W starting), a refrigerator (400 / 1,200 W), a coffee maker (600 W), a TV (70 W) and lights (60 W). Running total = 1,800 + 400 + 600 + 70 + 60 = 2,930 W. The air conditioner adds the biggest surge, 2,800 − 1,800 = 1,000 W, so starting = 3,930 W. With a 20% margin, look for at least 3,516 W running and 4,716 W starting.
(Cummins' version also includes two 10 W phone chargers, giving 2,950 W and 3,950 W.)
About the margin
Cummins only says to pick a generator whose ratings are above your totals. The 20% default here is a cushion, so the generator isn't run flat out and you have room for something you forgot. It's a choice, not a rule: set it to 0 to see the bare minimum.
Safety and limits
- Never run a generator indoors, in a garage or near windows: carbon monoxide kills. Keep it well away from the house.
- Use a transfer switch installed by an electrician to connect to home wiring. Back-feeding through an outlet can kill utility workers.
- Nameplate watts are best. If a label lists only amps, watts ≈ volts × amps. Well pumps and central air can have very large starting loads; check the maker's figures.