CFM calculator

Find the CFM for a room from its size and air changes per hour, size a bathroom fan the HVI way, or get the airflow through a duct from its size and air speed.

Private: calculated on your device. Nothing you type is sent anywhere.

Next: Know the CFM? Size the duct with the duct size calculator.

Three ways to find CFM

CFM is cubic feet of air per minute.

Room: CFM = length × width × height × ACH ÷ 60
Bathroom up to 100 sq ft: CFM = floor area × 1
Bathroom over 100 sq ft: 50 CFM per toilet, shower or tub, 100 CFM per jetted tub
Duct: CFM = velocity (ft/min) × cross-section area (sq ft)

Air changes per hour (ACH) is how many times the room's full volume of air is replaced each hour. Air flow per hour = ACH × volume (Engineering ToolBox), and dividing by 60 turns it into per minute.

The bathroom rule comes from the Home Ventilating Institute (HVI): 1 CFM per square foot for bathrooms up to 100 sq ft, which HVI notes is about 8 air changes an hour, and the fixture count for larger bathrooms.

Worked examples

Room: a 14 × 12 ft room with 8 ft ceilings is 1,344 cubic feet. At 6 air changes per hour: 1,344 × 6 ÷ 60 = 134.4 CFM.

Bathroom: an 8 × 10 ft (80 sq ft) bathroom needs an 80 CFM fan. A 120 sq ft bathroom with a toilet, a shower and a jetted tub needs 50 + 50 + 100 = 200 CFM.

Duct: an 8 in round duct has an area of π × (4 ÷ 12)² = 0.349 sq ft. At 800 ft/min it carries 800 × 0.349 = 279 CFM.

Typical air change rates

SpaceAir changes per hour
Residences (general)1–2
Garages, storage4–6
Laundries10–15
Kitchens15–60
Homes, night cooling10–18

Figures from the Engineering ToolBox. Codes and standards such as ASHRAE 62.2 set the required ventilation for homes; follow your local code.

Getting a realistic number

  • Fan ratings drop with duct length. A fan's rated CFM is at a low static pressure. Long or crooked ducts deliver less, so pick a fan rated above the target or use short, straight, smooth ducts.
  • Velocity in ducts: residential supply trunks commonly run at about 700 to 900 ft/min and branches at 500 to 700 ft/min (HVAC School). Faster air is noisier.
  • Measuring: airflow hoods and anemometers give the real CFM at a grille.

Sources

How we checked this

Before every update, this calculator is run in a real browser with these known answers, and it must match all of them:

  • 14 × 12 × 8 ft room at 6 ACH: 134.4 CFM ✓
  • 80 sq ft bathroom: 80 CFM (HVI 1 CFM per sq ft) ✓
  • 120 sq ft bathroom, toilet, shower, jetted tub: 200 CFM ✓
  • 8 in round duct at 800 ft/min: 279.3 CFM ✓
  • 12 × 8 in duct at 600 ft/min: 400 CFM ✓
  • Edge: a big bathroom with no fixtures asks for them ✓

Last checked October 26, 2026. Spotted something wrong? The math is done in your browser with the formula shown on this page, so you can check any result by hand.

Add this calculator to your website (free)

Paste this code into any web page. The calculator works on your page, resizes itself, has no ads and no tracking cookies, and nothing your visitors type is sent anywhere. More about embedding.

Questions people ask

How do I calculate CFM for a room?

Multiply length × width × height to get cubic feet, multiply by the air changes per hour you want, and divide by 60.

What size bathroom fan do I need?

HVI's guideline is 1 CFM per square foot for bathrooms up to 100 sq ft, so 80 CFM for an 80 sq ft room. Larger bathrooms add 50 CFM per toilet, shower or tub and 100 CFM per jetted tub.

How many CFM is a 6 inch duct?

At 700 ft/min, a 6 in round duct (0.196 sq ft) carries about 137 CFM; at 900 ft/min, about 177 CFM.

What is ACH?

Air changes per hour: how many times a space's whole volume of air is replaced in an hour.

How do I convert CFM to air changes per hour?

ACH = CFM × 60 ÷ room volume in cubic feet. 134.4 CFM in a 1,344 cu ft room is 6 ACH.